AS/NZS 5601.2:2020 Section 7 · Minimum free area, Clause 7.3.1
Use the input from each rating plate. Include cookers.
| Appliance | MJ/h | Counted in U? |
|---|
Fixed on or next to both the high and low vents. Characters at least 4 mm high (Cl 7.7).
Total permanent ventilation is the greater of 4 000 mm² or V = (610 × U) + (650 × P) (Cl 7.3.1).
U is the input of every appliance in the space except room-sealed ones, cookers included, in MJ/h. A gas fridge in a sealed recess counts as room-sealed (Note 4). An appliance in a locker or compartment outside the caravan floorplan isn't counted as being in the caravan (Note 2).
If every appliance is room-sealed, the minimum is 4 000 mm² (Cl 7.3.1).
Unit conversion: 1 kW = 3.6 MJ/h, 1 000 BTU/h = 1.055 MJ/h (Note 5).
Mesh and louvres cut the free area. As a guide, double the area where mesh is used (Note 6).
This is the minimum for safety and should be exceeded where possible. It doesn't replace normal opening windows (Note 3). For mobile catering vehicles use AS/NZS 5601.1 instead (Note 7).
Calculated tool for checking your work. Confirm against AS/NZS 5601.2 and the appliance manufacturer's instructions.